Features
- universal intrinsically safe isolating repeater of current signals 0/4 ÷ 20 mA with 0,07 % accuracy and with option voltage output 0 ÷ 10 V
- galvanic separation input and output signal
- for supply sensors with output 0/4 ÷ 20 mA e.g. CLM-36Xi, ULM-55Xi etc. in explosive area up to zone 0 (acc. to EN 60079-10)
- option bi-directional transmission of communication signal HART®
- classifi cation of explosive-proof performance
- EEX II (1)G [EEx ia] IIB / IIC
- EEX I (M1) [EEx ia] I
- instalation on DIN rail 35 mm
- variants for 24V and 230V
Universal intrinsically safe isolating repeater IRU-420 is designed for supply transducers of physical value (sensors) in explosive areas and for conversion of input signal 0/4 ÷ 20 mA to output signal. Galvanic separation of current signal 0/4 ÷ 20 mA from transducer in explosive area to transducer in non-explosive area.
Variants:
IRU - 420 - I - convert's signal 0/4 ÷ 20 mA to 0/4 ÷ 20 mA
IRU - 420 - H - convert's signal 4 ÷ 20 mA to 4 ÷ 20 mA and bi-directional transmission of HART® communication signal
IRU - 420 - U - convert's signal 4 ÷ 20 mA to 0 ÷ 10V
List of all variants
variants 24 V:
- IRU-420-I-24V
- IRU-420-H-24V
- IRU-420-U-24V
variants 230 V:
- IRU-420-I-230V
- IRU-420-H-230V
- IRU-420-U-230V
Safety, protections, compatibility and explosion proof
Isolating repeater is equipped with protection against input and output current overload.
Working areas acc. to EN 60079-10 - non-explosive, or installation in fl ameproof enclosure "d".
Connection to supply can be only through fuse or overcurrent circuit breaker - max. 16 A.
Unit is sheltered by fuse T80 mA (variant 230 V) and T500 mA (variant 24 V).
Electrical equipment of protection group II.
Electrical safety according to EN 61010 - 1.
EMC according to EN 55022, EN 61326, EN 61000-6-2, EN 61000-4-2, -3, -4, -5, -6, -11.
Intrinsically safety according to EN 50014 and EN 50020.
Approval: FTZU - AO 210 Ostrava - Radvanice Certifi cate No.: FTZU 05 ATEX 0167X